Performance Specifications |
| |
|
Alarm
settings |
Dual-level |
|
Battery
life (Pyrolyzer) |
1 hour 30
minutes when fully charged |
|
Operation
Temperature |
-4° F to
104° F (-20° C to +40° C) |
|
Relative
humidity |
20 - 90% RH
non-condensing |
|
Pressure |
700 kPa to
1300 kPa |
|
Sample
tubing |
1/4" OD
3/16" ID |
|
Response
time |
<30 seconds
(10 m tubing length) |
|
Operational
sensor cell life |
>1 year
(under normal conditions) |
|
Sensor
service interval |
6 months |
|
Applicable
standards |
RFI / EMC:
EN 55022 EN 50082-2 |
|
Graphic
display |
122 x 32
dots with back light |
|
LED
indication |
Alarm,
fault, power status |
|
Acoustical
alarm |
Continuous
/ alternating buzzer signal |
|
| |
|
Facility Requirements |
| |
|
Network
interface (P/N 9753-04xx) |
|
|
Network |
Standard
LonTalk®
Protocol |
|
|
Data
transmission |
78 kBit per
second |
|
|
Wiring
topologies |
Free, (e.g.
Bus, Star, Loop or mixed) (2 x 2 x
1.0 mm / 17 AWG) |
|
Electrical
supply |
12 VDC
rechargeable battery |
|
Protection
class |
IP 30 |
Overall
dimensions (H x W x D) |
9.3 x 5.9 x
9.3 in 235 x 150 x 235 mm |
|
Weight |
11.5 lbs
(5.2 kg) |
|
| |
| Network interface (P/N 9753-02xx) |
| |
Interface |
4 - 20 mA |
| |
Fault range
|
0 ... 2 mA |
| |
Warning
mode |
2.8 ... 4 mA @ 0.1 Hz |
| |
Maintenance
mode |
2.4 ... 4 mA @ 1 Hz |
| |
Wiring |
Shielded (tinned copper braid)
3 wire cable
(3 - 1.0 mm / 17 AWG) |
|
|
Protection class
|
IP 30 |
|
Overall Dimensions |
H x W x D |
| |
235 x 150 x 235 mm |
| |
9.3 x 5.9 x 9.3 in. |
|
Weight |
5.2 kg (11.5 lbs.) |
|
| |
|
Outputs and Communications |
| |
| Life Safety
Network - LonWorks® |
| Facility
computer -
MST DVS
Software |
| MST Relay
Output Controller |
| MST local Info
Display |
| FMS 8700 and
FMS 8710 MST Controllers |
| PLC / SCADA
Communications |