Performance Specifications |
| |
|
Alarm
settings |
Dual-level
user settable |
|
Operating
temperature |
-4° F to
104° F (-20° C to 40° C) |
|
Relative
humidity |
20 - 90% RH
non condensing |
|
Pressure |
700 - 1100
hPa |
|
Operational
sensor cell life |
>1 year
(standard conditions) |
|
Application
standards |
RFI / EMC:
EN 55022, EN 50082-2
ATEX: EX II 2 G EEX d ib II C T4 |
|
| |
|
Facility Requirements |
| |
|
Electrical
supply |
12 or 24
VDC |
|
Power
consumption |
max. 2.4 W |
|
Wiring |
|
|
|
Standard
version |
Shielded 4
wire cable
(2 x 2 x 0.5 mm2 / 17 AWG |
|
|
Relay
version |
Shielded 10
wire cable
(5 x 2 x 0.5 mm2 / 17 AWG |
|
Digital
Sat-Ex |
|
| |
Network |
standardized LonTalk® |
| |
Data
transmission |
78 kBits
per second |
|
Analog
Sat-Ex |
|
| |
Interface |
4 - 20 mA |
| |
Fault |
0 - 2 mA |
|
Alarm relay
outputs (Optional) |
|
| |
Contacts |
3 x SPST |
| |
Ratings |
250 VAC /
30 VDC, 2 A |
|
Enclosure
construction |
Explosion
proof housing |
|
Protection
class |
IP 66 |
|
Overall
dimensions
H x W x D |
11.8 x 5.6
x 5.6 in
300 x 143 x 143 mm |
|
|
Weight |
< 7.7
lbs (3.5 kg) |
|
Mounting |
4 Nut,
Flanged eyelet |
|
| |
|
Outputs and Communications |
| |
| Life
safety Network - LonWorks® |
|
|
Facility computer -
MST DVS software |
|
FMS 8700 and FMS 8710 MST Controllers |
|
PLC / SCADA communication |
| |
|
Configurations |
| |
|
Sat-Ex 4 -
20 mA |
Analog,
Toxic, Corrosive |
|
Sat-Ex 4
-20 mA / R |
Analog,
Toxic, Corrosive, Relay outputs |
|
Sat-Ex 4
-20 mA / C |
Analog,
Combustible |
|
Sat-Ex 4 20
mA / R / C |
Analog,
Relay outputs, Combustible |
|
Sat-Ex FTT
|
Digital,
Toxic, Corrosive |
|
Sat-Ex FTT
/ R |
Digital,
Toxic, Corrosive, Relay outputs |
|
Sat-Ex FTT
/ C |
Digital,
Combustible |
|
Sat-Ex FTT
/ R / C |
Digital,
Relay outputs, Combustible |
|
|
|
|