MST Technology Website

Europe



Extractive Gas Detector, Pyrolyzer Gas Detector Europe

MST XT Series Technical Overview

 

 

Performance Specifications

 
Alarm settings Dual-level user settable
Power consumption approx. 60 W
Operating temperature -4° F to 104° F (-20° C to 40° C)
Relative humidity 20 - 90% RH non condensing
Operational sensor cell life >1 year (under normal conditions)
Calibration intervals 6 months
Application standards RFI / EMC: EN 55022
EN 50082-2
 

Facility Requirements

 
Satellite XT
Satellite XT Extractive
12 or 24 VDC
Satellite XT Pyrolyzer 12 or 24 VDC and 90 to 240 VAC
Digital Satellite XT  
  Network Standard LonTalk®  Protocol
  Data transmission 78 kBits per second
  Wiring topologies Free (e.g. Bus, Star, Loop or mixed)
  Wiring Shielded 4 wire cable
2 x 2 x 1.0 mm2 / 17 AWG
Approx. 2 m delivered with instrument
Analog Satellite XT  
  Interface 4 - 20 mA
  Fault 0 - 2.0 mA
  Wiring Shielded 3 wire cable
3 x 1.0 mm2 / 17 AWG
approx. 2 m delivered with instrument
Enclosure construction  
  Satellite XT Metalized ABS
  Extractive Module XT ABS
  Pyrolyzer Module XT Coated metal
Protection class
  Satellite XT IP 52 (IP 65 optional)
  Extractive Module XT IP 54
  Pyrolyzer Module XT IP 30
Overall dimensions H x W x D
  Satellite XT 95 x 145 x 50 mm
3.7 x 5.7 x 2.0 in
  Extractive Module XT 95 x 75 x 50 mm
3.7 x 2.9 x 2.0 in
  Satellite Extractive and
Pyrolyzer Module XT
95 x 225 x 145 mm
3.7 x 8.8 x 5.7 in
Weight approx. 2 kg for all three modules
Mounting DIN rail only
 

Outputs and Communications

 
Life safety Network - LonWorks®
Facility computer - MST DVS software
FMS 8700 and FMS 8710 MST Controllers
PLC / SCADA communication
 
 
 
Product Information  
   
 
 

XT Series

bullet XT Series
bullet Detectable Gases
bullet Technical Overview
bullet Quick Facts
Printable Data
bullet Brochure
Application Notes
bullet In-Situ vs. Extractive
Models Numbers
bullet 20404-0100 Extractive Series
bullet 20408-0100 Pyrolyzer Series
Contact a sales professional
 
 

Extractive Gas Detector, Pyrolyzer Gas Detector Europe

Contact    Impressum    Add to favorites     Site Suggestions   Recommend Us   Privacy Statement
MST Technology - International Sites:  Global   
Europe     North America     Asia

Honeywell International    Honeywell Analytics


© Honeywell Analytics 2008

ISO 9001: 2000