Performance Specifications |
| |
|
Alarm
settings |
Dual-level
user settable |
|
Power
consumption |
max. 1.8 W |
|
Operating
temperature |
-4° F to
104° F (-20° C to 40° C) |
|
Relative
humidity |
20 - 90% RH
non condensing |
|
Operational
sensor cell life |
>1 year
(under normal conditions) |
|
Calibration
intervals |
6 months
(depending on cell) |
|
Application
standards |
RFI / EMC:
EN 55022 EN 50082-2 |
|
| |
|
Facility Requirements |
| |
|
Electrical
supply |
12 or 24
VDC |
|
Digital
Satellite XT |
|
|
|
Network |
Standard
LonTalk® Protocol |
|
|
Data
transmission |
78 kBits
per second |
|
|
Wiring
topologies |
Free (loop
recommended) |
|
|
Wiring |
Shielded 4
wire cable 2 x 2 x 1.0 mm2
/ 17 AWG Approx. 2 m delivered with
instrument |
|
Analog
Satellite XT |
|
| |
Interface |
4 - 20 mA |
| |
Fault |
0 - 2.0 mA |
| |
Wiring |
Shielded 3
wire cable 3 x 1.0 mm2 /
17 AWG approx. 2 m delivered with
instrument |
|
Enclosure
construction |
Metalized ABS |
|
Protection
class |
IP 52 (IP 65 optional) |
|
Overall
dimensions
H x W x D |
95 x 145 x
50 mm 3.7 x 5.7 x 2.0 in |
|
|
Weight |
17 oz
(480 g) |
|
Mounting |
DIN rail
(standard)
4 Nuts (optional) |
|
| |
|
Outputs and Communications |
| |
| Life
safety Network - LonWorks® |
|
|
Facility computer -
MST DVS software |
|
FMS 8700 and FMS 8710 MST Controllers |
|
PLC / SCADA communication |
| |